XLPE INSULATED PVC SHEATHED ARMOURED CABLES


600/1000 V - COPPER CONDUCTOR XLPE INSULATED PVC SHEATHED STEEL WIRE ARMOURED CABLES (CU/XLPE/PVC/SWA/PVC)


CU/XLPE/PVC/SWA/PVC is a XLPE insulated, PVC bedded, steel wire armoured and PVC
sheathed auxiliary cable with circular, compacted and stranded annealed copper conductors
complying with BS 6360 class 2. The cable is designed according to BS 5467. The armour is
a single layer of galvanized steel wires.
*Circular solid conductor (Class 1).

Usage characteristics

   Minimum installation temperature

0

 °C

   Maximum operating temperature

90

 °C

   Short-circuit max. conductor temperature

250

 °C

   Flame retardant as per

IEC 60332-1

   Bending factor when laying

6

 (xD)

TWO CORE CU/XLPE/PVC/SWA/PVC

Nominal Area of Conductor

Thickness of Insulation 

Thickness of Extruded Bedding

Diameter of Armour Wire

Thickness of Outer Sheath

Approx. Overall Diameter

Approx. Cable Weight

Sqmm

mm

mm

mm

mm

mm

Kg/Km

1.5*

0.7

0.8

0.9

1.3

12.8

305

1.5

0.7

0.8

0.9

1.3

13.2

325

2.5*

0.7

0.8

0.9

1.4

13.8

360

2.5

0.7

0.8

0.9

1.4

14.2

375

4

0.7

0.8

0.9

1.4

15.2

440

6

0.7

0.8

0.9

1.4

16.4

520

10

0.7

0.8

0.9

1.5

18.0

670

16

0.7

0.8

1.25

1.5

20.9

965

25

0.9

0.8

1.25

1.6

24.3

1310

35

0.9

1.0

1.6

1.7

27.8

1810

50

1.0

1.0

1.6

1.8

30.9

2070

70

1.1

1.0

1.6

1.9

34.7

2650

95

1.1

1.2

2.0

2.0

39.9

3640

120

1.2

1.2

2.0

2.1

43.5

4330

150

1.4

1.2

2.0

2.2

47.3

5140

185

1.6

1.4

2.5

2.4

53.1

6570

240

1.7

1.4

2.5

2.5

58.7

8050

THREE CORE CU/XLPE/PVC/SWA/PVC

Sqmm

mm

mm

mm

mm

mm

Kg/Km

1.5

0.7

1.0

0.90

1.8

14.5

391

2.5

0.7

1.0

0.90

1.8

15.5

435

4

0.7

1.0

0.90

1.8

17.0

550

6

0.7

1.0

1.25

1.8

18.5

660

10

0.7

1.0

1.25

1.8

20.4

900

16

0.7

1.0

1.25

1.8

23.4

1260

25

0.9

1.0

1.60

1.8

25.0

1630

35

0.9

1.0

1.60

1.8

27.0

1995

50

1.0

1.0

1.60

1.9

30.5

2520

70

1.1

1.2

2.00

2.0

35.0

3585

95

1.1

1.2

2.00

2.2

38.5

4590

120

1.2

1.2

2.00

2.3

42.0

5530

150

1.4

1.4

2.50

2.5

47.5

7000

185

1.6

1.4

2.50

2.6

52.0

8460

240

1.7

1.6

2.50

2.8

62.0

10550

FOUR CORE CU/XLPE/PVC/SWA/PVC

Nominal Area of Conductor

Thickness of Insulation 

Thickness of Extruded Bedding

Diameter of Armour Wire

Thickness of Outer Sheath

Approx. Overall Diameter

Approx. Cable Weight

Sqmm

mm

mm

mm

mm

mm

Kg/Km

1.5

0.7

1.0

0.90

1.8

15.3

433

2.5

0.7

1.0

0.90

1.8

17.0

519

4

0.7

1.0

0.90

1.8

18.5

635

6

0.7

1.0

1.25

1.8

19.8

735

10

0.7

1.0

1.25

1.8

22.0

1026

16

0.7

1.0

1.25

1.8

26.0

1640

25

0.9

1.0

1.60

1.8

27.5

2020

35

0.9

1.0

1.60

1.8

30.5

2475

50

1.0

1.0

1.60

1.9

33.5

3100

70

1.1

1.2

2.00

2.0

38.5

4480

95

1.1

1.2

2.00

2.2

43.0

5735

120

1.2

1.2

2.00

2.3

49.0

7460

150

1.4

1.4

2.50

2.5

53.0

8810

185

1.6

1.4

2.50

2.6

59.0

10780

240

1.7

1.6

2.50

2.8

68.0

13600

4 CORE CABLES WITH REDUCED NEUTRAL (3 & 1/2 CORE) CU/XLPE/PVC/SWA/PVC

Nominal
Area of Conductor

Insulation Thickness

Diameter Over Bedding

Steel Wire Armor Diameter

Diameter Over Armor

Outer Sheath Thickness

Overall Diameter

Approxi-
mate
Weight

mm2

mm

mm

mm

mm

mm

mm

kg/km

3 X 10 / 6

0.7
0.7

14.8

1.25

17.3

1.8

21.1

1055

3 X 16 / 10

0.7
0.7

17.3

1.25

19.8

1.8

23.6

1380

3 X 25 / 16

0.9
0.7

21.1

1.6

24.3

1.8

28.1

2075

3 X 35 / 16

0.9
0.7

23.1

1.6

26.3

1.8

30.1

2470

3 X 50 / 25

1.0
0.9

27.0

1.6

30.2

1.9

34.2

3180

3 X 70 / 35

1.1
0.9

31.7

2.0

35.7

2.1

40.1

4530